ABB UNS2881B-P,V1 3BHE009319R0001向船舶应用推进
滚动LED状态指示灯
滚动LED显示屏指示模块的工作状态,如下所示:初始化消息
代码消息
启动/DDOK模块正在初始化
Ladd模块正在等待来自的所需模块配置数据
用于配置应用程序端口的梯形图逻辑等待处理器连接模块在初始化期间未连接到处理器
处理器上未加载示例梯形图逻辑或AOI
模块位于不同的插槽中在梯形图逻辑/AOI中配置
处理器未处于RUN或REM RUN模式
上次配置:<日期>表示模块更改其IP的最后日期
住址您可以通过以下方式更新模块日期和时间
模块的网页,或使用可选MVI56E插件指示
通电和每次重新配置后,模块将显示应用程序端口的配置。这个信息包括:客户端模块未获得足够电源或不安全插入机架。配置期间也可能关闭下载
绿色MVI56E-SIE工作正常。红色最常见的原因是模块检测到
应用程序端口操作期间的通信错误。
以下情况也可能导致红色LED:
固件正在启动期间初始化
固件检测到板载硬件问题
启动期间
启动期间应用程序端口硬件故障
模块正在关闭
由于ColdBoot或WarmBoot,模块正在重新启动梯形图逻辑或调试菜单的请求模块未获得足够的电源或不安全插入机架。绿色模块工作正常。
红色模块检测到内部错误或正在已初始化。如果LED保持红色超过10秒模块不工作。将其从机架上拆下并重新插入重新启动其内部程序。
ERR红色OFF蓄电池电压正常且工作正常。
ON蓄电池电压低或不存在蓄电池。允许电池充电,将模块插入机架24小时。如果ERR LED仍不熄灭,请联系ProSoft技术,因为电池不是用户可维修的部件。
Scrolling LED Status Indicators
The scrolling LED display indicates the module's operating status as follows:
Initialization Messages
Code Message
Boot / DDOK Module is initializing
Ladd Module is waiting for required module configuration data from
ladder logic to configure the application port(s)
Waiting for Processor Connection Module did not connect to processor during initialization
Sample ladder logic or AOI is not loaded on processor
Module is located in a different slot than the one
configured in the ladder logic/AOI
Processor is not in RUN or REM RUN mode
Last config: <date> Indicates the last date when the module changed its IP
address. You can update the module date and time through
the module’s web page, or with the Optional MVI56E Add-On
Instruction.
After power up and every reconfiguration, the module will
display the configuration of the application port(s). The
information consists of:
Client The module is not receiving adequate power or is not securely
plugged into the rack. May also be OFF during configuration
download.
GREEN The MVI56E-SIE is working normally.
RED The most common cause is that the module has detected a
communication error during operation of an application port.
The following conditions may also cause a RED LED:
The firmware is initializing during startup
The firmware detects an on-board hardware problem
during startup
Failure of application port hardware during startup
The module is shutting down
The module is rebooting due to a ColdBoot or WarmBoot
request from the ladder logic or Debug Menu The module is not receiving adequate power or is not securely
plugged into the rack.
GREEN The module is operating normally.
RED The module has detected an internal error or is being
initialized. If the LED remains RED for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.
ERR Red OFF The battery voltage is OK and functioning.
ON The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If ERR LED still does not go off, contact ProSoft
Technology, as the battery is not a user-serviceable item.