R(un)和F(ault)指示灯均不亮CI858板正在重新启动或配置过程中。留出时间完成。如果情况持续存在,并且CEX总线上没有其他单元LED点亮:•检查是否将包括CI858在内的有效硬件配置下载到控制器。•检查处理器单元内的CEX总线保险丝。•启动来自处理器单元的复位信号(INIT)。•更换CI858装置。F(ault)LED点亮装置错误或正在初始化。检查所有电缆和连接器是否损坏、松动或连接不良。•必要时进行维修。数据库总线;Rx1 LED点亮(不闪烁)装置未接收数据。•检查所有电缆和连接。•更换CI858装置。数据库总线;Rx1 LED熄灭没有信号发送到装置或装置错误。•检查所有电缆和连接。•更换CI858装置。数据库总线;Tx1 LED亮起(不闪烁)装置未传输数据。•检查CB是否有故障信息。•如果CB中没有故障消息,则更换CI858单元。
Neither R(un) nor F(ault) LEDs are ON The CI858 board is in the process of being restarted or configured. Allow time for this to finalize If the condition persists, and no other unit LED on the CEX-Bus is lit: • Check that a valid HW configuration including the CI858 is downloaded to the controller. • Check the CEX-Bus fuse inside the processor unit. • Initiate a reset signal (INIT) from the processor unit. • Replace the CI858 unit. F(ault) LED is ON Unit error or initializing. Check all cables and connectors for damage and loose or poor connections. • Repair as necessary. Dbus;Rx1 LED is ON (not flashing) The unit is not receiving data. • Check all cables and connections. • Replace the CI858 unit. Dbus;Rx1 LED is OFF No signals are sent to the unit or unit error. • Check all cables and connections. • Replace the CI858 unit. Dbus;Tx1 LED is ON (not flashing) The unit is not transmitting data. • Check the CB for a failure message. • If there is no failure message in the CB replace the CI858 unit.