在同一控制网络内重复使用从冗余配置中更换的CPU模块可能会由于MAC和IP地址处理而导致控制网络问题。参见第49页冗余配置中的MAC和IP地址处理。除非已知被替换的模块和先前与其一起在冗余配置中工作的模块从先前的相互地址交换中恢复,否则不应实现这种重用。建议设置IP配置会话,然后使用“恢复出厂设置”选项,然后重新分配IP地址或分配新的IP地址。使用BC810进行配置时,不要在5.0之前的版本中在线更换RCU链接电缆。支持在线更换还取决于硬件产品版本级别。有关详细信息,请参阅发行说明(3BSE021377*)。如果证明支持在线更改,在考虑了上述警告后,BC810外部提供24V电源,则可以遵循与不带BC810的配置相同的步骤。
Reuse of CPU modules replaced from redundant configurations within the same control network, might cause control network problems due to the MAC and IP address handling. See MAC and IP Address Handling in Redundant Configuration on page 49. Such reuse should not be fulfilled unless both the replaced module and the module previously acting together with it in redundant configuration are known to be restored from the previous mutual address swap. It is recommended to set up an IP-config session and use the “Restore factory settings” option subsequently followed by reassignment of the IP address or assignment of a new IP address.In Configuration with BC810 Do not replace the RCU link cable online in a previous version than 5.0. The support for online replacement also depends on hardware Product Revision levels. Please consult Release Notes (3BSE021377*) for detailed information.If online change proves to be supported, after the caution above has been considered, and the BC810s are externally supplied with 24V the same steps as in configuration without BC810 can be followed.