连接至电缆进入的360°盖。•连接两端的护罩。屏蔽电缆电位不相同接地平面1接地平面2接地板另一栋建筑中的接地板0.1μF/250 V距离越长,接地电位可能不同。在这种情况下,屏蔽只能在一端连接。一个很好的选择是通过0.1µF/250 V塑料电容器将屏蔽的另一端连接到地。然后,在HF方面两端都接地,但在LF方面仅一端接地,从而避免50/60Hz接地回路。金属柜金属柜端子或连接器端子或连接器EMC电缆密封套塑料电缆密封套屏蔽电缆短距离钢制电缆夹屏蔽ed to the cover 360° where the cable enters. • Connect the shield at both ends. Shielded cable Not same potential Ground plane 1 Ground plane 2 Ground plate Ground plate in another building 0.1 μF/250 V With longer distances, there is a risk that the ground potential may be different. In that case, the shield should only be connected at one end. A good alternative is to connect the other end of the shield to the ground via a 0.1 µF/250 V plastic capacitor. Both ends are then connected to the ground in terms of HF, but only connected to the ground at one end in terms of LF, thus avoiding the 50/60 Hz grounding loops. Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Short distance Cable clamp in steel Shielded