The calculated value may be increased to allow more acyclic
traffic, if necessary.If there are other masters on the bus, the
calculated value has to be increased for the time these other
masters need for their cyclic and acyclic communication. Refer to
the configuration of these masters.
In a multi-master system all masters must use the same
value for TTR.
GAP factor
(GAP)
This parameter defines the number of token rotations between
GAP maintenance cycles.
The current version of the CI854/CI854A always uses a
value of 1 independent of the value entered here.Highest
station
address
(HSA)
This parameter defines the highest station address on the
PROFIBUS. Set the parameter to at least the highest number of
node addresses configured for all masters and slaves present on
the bus.