SAGEMCOM 252720938AB工控控制卡件
这些参数用于设置CI854/CI854A。通常,大多数参数无需更改。标有*的参数将由Control Builder计算(在下载期间),但可能需要调整,因为使用了特殊的从设备、中继器或段耦合器。端地址这是主设备的PROFIBUS地址,范围可以在1-125之间。此地址必须与所有其他从属地址不同,否则会生成编译错误。根据配置中的设备编号为从属设备分配地址。使用多主系统,确保与其他主系统及其从属系统之间没有寻址冲突。波特率支持的波特率为9.6;19.2; 93.75; 187.5; 500; 1500; 3000; 6000和12000千比特/秒。不支持波特率31.25和45.45 kbit/s。默认值为1.5 Mbit/s。较高的值需要仔细考虑正确的电缆安装。所有从属设备必须支持波特率设置。某些从设备在波特率更改后需要手动复位。
These parameters are used to set up CI854/CI854A. Normally, most of the
parameters need not be changed. Parameters marked with a * will be calculated (during download) by the Control Builder, but may need to be adjusted due to
special slaves, repeaters, or segment couplers used.ode address This is the PROFIBUS address of the master which can be in the
range 1-125. This address must differ from all other slave
addresses, otherwise a compilation error is generated. Slaves are
assigned their addresses according to the device numbering in the
configuration. With multi-master systems ensure that there is no
addressing conflict with the other masters and their slaves.
Baudrate Supported baudrates are 9.6; 19.2; 93.75; 187.5; 500; 1500; 3000;
6000 and 12000 kbit/s. Not support are the baud rates 31.25 and
45.45 kbit/s. The default value is 1.5 Mbit/s. Higher values require
careful consideration of correct cable installation. All slave devices
must support baud rate setting. Some slaves require a manual
reset after change of the baud rate.