GE IC695CPU315-BB CPU模块
PROFIBUS线路B上无活动报警介质如果启用了线路冗余,则此警告反映主单元RxB LED的状态。30 16#4000000 CI854(A)错误警报高硬件故障在主单元上检测到硬件故障,例如RAM故障。31 16#8000000 0固件需要重新加载错误报警介质主单元不包含有效的固件。总线超时,可能是重复的从属地址(TTO)PROFIBUS的下层检测到超时。在波特率更改过程中,此错误可能会出现很短时间。如果仍然存在,则必须检查PROFIBUS连接和从属地址。总线同步故障,检查硬件(SYN)PROFIBUS的下层检测到同步错误。在波特率更改过程中,此错误可能会出现很短时间。如果仍然存在,请检查PROFIBUS硬件(电缆、连接器、从设备)。
No activity on
PROFIBUS line B
Warnin
g
Alarm Mediu
m
If line redundancy is enabled, this
warning reflects the state of the
RxB LED of the primary unit.
30 16#4000000
0
Hardware fail of
CI854 (A)
Error Alarm High A hardware failure has been
detected on the primary unit, for
example RAM failure.
31 16#8000000
0
Firmware needs
to be reloaded
Error Alarm Mediu
m
The primary unit does not contain
a valid firmware.Timeout on bus,
maybe duplicate
slave address
(TTO) The lower layer of the PROFIBUS
has detected a timeout. During a
baudrate change this error may
occur for a short time. If it remains,
the PROFIBUS connection and
slave addresses must be checked.Bus
synchronization
failure, check
hardware (SYN) The lower layer of the PROFIBUS
has detected a synchronization
error. During a baudrate change
this error may occur for a short
time. If it remains, check the
PROFIBUS hardware (cables,
connectors, slaves).