3HNA025019-001脉冲输入卡件
LED和显示器组合COPN状态
描述OK LED绿色,SYS LED为琥珀色。卡处于在线状态,DP Master正在清除模式下扫描,连接打开。OK LED为绿色,COMM和SYS关闭。板卡离线,连接打开。SYS和OK LED为绿色。通信关闭。卡处于在线状态,由DP主机在运行模式下扫描,连接打开。通信关闭。SYS LED为红色,OK LED为绿色。卡处于联机状态,DP主机未扫描该卡。用户参考指南SST-PB3S-CLX-RLL 28安装SST-PB3S-CLX-RLL从机©2014 Molex股份有限公司工业产品业务部,综合产品部文件版本:1.0,文件#:715-0109,模板版本:1.1,模板35;:QMS-06-045使用,复制或披露本文件或其中包含的任何信息均受本文件第ii页的限制。4.5.1显示表下表显示了滚动LCD显示信息和说明:表8:SST-PB3S-CLX-RLL显示显示含义/说明版本x.xx加电消息。此消息在通电期间短暂出现。x、 xx是固件版本。序列号无效序列号尚未在此模块上编程。CLX INIT FALT 0xYY ControlLogix初始化错误。ControlLogix背板启动例程失败,故障代码为YY(十六进制)。CONNCLSD没有打开的ControlLogix背板连接。NVLD XMIT SIZE传输大小无效。新连接的传输数据大小与现有连接的大小不匹配。NVLD OUT CNPT输出连接点无效。NVLD RCV SIZE接收大小无效。连接的接收数据大小无效。
NVLD RCV BUFF接收缓冲区无效
无法分配接收缓冲区。这不应该发生。CONN BLKED连接被阻止(不允许)。连接管理器处于“不允许连接”状态。这不应该发生。DUPLCONN DTCT检测到重复连接。连接已打开。连接管理器中的RSRC ERR1 INCM资源错误#1:内存不足。这不应该发生。NVLD FWD OPEN向前打开无效。CM无法解析转发打开。可能是关键段不匹配。NVLD SRVC CODE服务代码无效。CLX Forward Open中的服务代码无效。WDOG监视器超时。模块监视器超时。OFPT从属固件操作故障。背板OK SST-PB3S-CLX-RLL位于已通电但未在CLX控制器中配置的机架中。引导SST-PB3S-CLX-RLL只是加电和初始化。COPN连接打开。MULT多个处理器正在尝试连接到从机。IDSMS存在Profibus从机ID不匹配。DP主设备试图用错误的从设备ID配置模块5.1 PB3S状态寄存器本地:插槽:S。数据[0],AOP标记本地:插槽:S。PfbStatus状态区域中的第一个16位INT是卡状态寄存器。下表显示了可能的状态寄存器值。表9:PfbStatus状态名称含义/描述值STS_NO_ERROR SST-PB3S-CLX-RLL没有错误0x0000 STS_BAD_BAD配置的波特率无效0x0002 STS_BAD_STN_ADR配置的站地址无效0x0003 STS_BAT_HI_STN_ADR配置最高站地址无效x0004 STS_CFG_INTERNAL_ERROR0x0080 STS_OUT_OF_APBS SST-PB3S-CLX-RLL已用完内部资源0x0081 STS_HEAP_ALLOC_FAIL SST-PB3CLX-RLL已经用完内部资源x0083 STS_SH_HEAP_ALLOC_FAIL如果状态寄存器包含STS_CFG_internal_ERROR(80h),则从机上存在内部错误。记录ErrInternal和errArg寄存器的内容,并联系技术支持。ErrInternal存储在状态区偏移量24的高位字节中。ErrArg存储在状态区域偏移量25的低位字节中。如果状态寄存器包含STS_HEAP_ALLOC_FAIL(83h)或STS_SH_HEAP_ALL(84h),则在分配内存时存在内部错误。联系技术支持。5.2从属固件版本从属固件的版本号存储在状态区域偏移1中。例如,如果值对应的字为0800h,则固件为版本8.00。SST-PB3S-CLX-RLL用户参考指南系统诊断31©2014 Molex股份有限公司工业产品业务部,集成产品部文件版本:1.0,文件#:715-0109,模板版本:1.1,模板编号:QMS-06-045使用、复制或披露本文件或其中包含的任何信息均受本文件第ii页的限制。5.3诊断计数器表10:诊断计数器名称位置含义/描述DiagInd本地:插槽:S。数据[07]总指示DiagInd计数器,寄存器本地:插槽:S。数据[07],统计总指示,即未经请求的消息
LED and display combined COPN status
Description The OK LED is green and the SYS LED is amber. The card is online, the DP Master is scanning in clear mode, and the connection is open. The OK LED is green and the COMM and SYS are off. The board is offline and the connection is open. The SYS and OK LEDs are green. Communication is off. The card is online, scanned by DP host in running mode, and the connection is opened. Communication is off. The SYS LED is red and the OK LED is green. The card is online, and the DP host has not scanned the card. User Reference Guide SST-PB3S-CLX-RLL 28 Installing SST-PB3S-CLX-RLL Slave © 2014 Molex Co., Ltd. Industrial Products Business Department, Integrated Products Department Document version: 1.0, Document #: 715-0109, Template version: 1.1, Template 35;: QMS-06-045 The use, reproduction or disclosure of this document or any information contained therein is subject to the restrictions of page ii of this document. 4.5.1 Display Table The following table shows the scrolling LCD display information and description: Table 8: SST-PB3S-CLX-RLL Display Meaning/Description Version x Xx power on message. This message appears briefly during power up. x. Xx is the firmware version. Invalid serial number Serial number has not been programmed on this module. CLX INIT FALT 0xYY ControlLogix initialization error. The ControlLogix backplane startup routine failed, and the fault code is YY (hexadecimal). CONNCLSD does not have an open ControlLogix backplane connection. The NVLD XMIT SIZE transmission size is invalid. The transmission data size of the new connection does not match the size of the existing connection. NVLD OUT CNPT output connection point is invalid. The NVLD RCV SIZE receive size is invalid. The receive data size of the connection is invalid.
NVLD RCV BUFF receive buffer is invalid
Unable to allocate receive buffer. This should not happen. CONN BLKED connection is blocked (not allowed). The connection manager is in the Disallow Connections state. This should not happen. DUPLCONN DTCT detected duplicate connections. The connection is already open. RSRC ERR1 INCM resource error # 1 in connection manager: Out of memory. This should not happen. NVLD FWD OPEN forward opening is invalid. CM cannot resolve forwarding open. The key segments may not match. The NVLD SRVC CODE service CODE is invalid. Invalid service code in CLX Forward Open. WDOG monitor timeout. The module monitor timed out. OFPT slave firmware operation failure. The backplane OK SST-PB3S-CLX-RLL is located in a rack that is powered up but not configured in the CLX controller. Booting SST-PB3S-CLX-RLL is just power on and initialization. The COPN connection is open. MULTMultiple processors are attempting to connect to the slave. There is a Profibus slave ID mismatch in IDSMS. The DP master attempted to configure the module 5.1 PB3S status register with the wrong slave ID Local: Slot: S. Data [0], AOP flag local: slot: S. The first 16 bit INT in the PfbStatus status area is the card status register. The following table shows the possible status register values. Table 9: Meaning of PfbStatus Name/Description Value STS_ NO_ ERROR SST-PB3S-CLX-RLL No error 0x0000 STS_ BAD_ Invalid baud rate of BAD configuration 0x0002 STS_ BAD_ STN_ Invalid station address configured by ADR 0x0003 STS_ BAT_ HI_ STN_ The highest station address configured by ADR is invalid x0004 STS_ CFG_ INTERNAL_ ERROR0x0080 STS_ OUT_ OF_ APBS SST-PB3S-CLX-RLL has used up internal resources 0x0081 STS_ HEAP_ ALLOC_ FAIL SST-PB3CLX-RLL has used up internal resources x0083 STS_ SH_ HEAP_ ALLOC_ FAIL If the status register contains STS_ CFG_ internal_ ERROR (80h), there is an internal error on the slave. Record the contents of the ErrInternal and errArg registers and contact technical support. ErrInternal is stored in the high byte of the status area offset 24. ErrArg is stored in the low byte of the status area offset 25. If the status register contains STS_ HEAP_ ALLOC_ FAIL (83h) or STS_ SH_ HEAP_ ALL (84h), there is an internal error when allocating memory. Contact Technical Support. 5.2 Dependent Firmware Version The version number of the dependent firmware is stored in the status area offset 1. For example, if the word corresponding to the value is 0800h, the firmware is version 8.00. SST-PB3S-CLX-RLL User Reference Guide System Diagnosis 31 © 2014 Molex Co., Ltd. Industrial Products Business Department, Integrated Products Department Document version: 1.0, Document #: 715-0109, Template version: 1.1, Template number: QMS-06-045 The use, copying or disclosure of this document or any information contained in it are subject to the restrictions of page ii of this document. 5.3 Diagnostic Counter Table 10: Diagnostic Counter Name Location Meaning/Description DiagInd Local: Slot: S. Data [07] indicates DiagInd counter in total, register local: slot: S. Data [07], statistical general indication, i.e. unsolicited message