模块上的32个绿色/黄色LED指示点1至32的on/OFF状态。当相应输出打开时,这些LED为绿色,如果输出出现故障,则为黄色。当相应的输出关闭时,它们将关闭。两个绿色/黄色LED指示每个隔离输出组是否有现场电源。如果现场功率在限制范围内,则为绿色。如果组内存在点故障,则为黄色。当现场电源不存在或超出操作限制时,它们将关闭。当模块的可拆卸接线板锁定到位时,模块的红色/绿色接线板LED为绿色。当接线板未锁定时,它为红色。如果存在不可恢复的模块故障,接线盒LED将闪烁。模块还向RX3i CPU发送添加端子块或丢失端子块消息,以报告端子块状态。设置输出默认值模块背面的DIP开关选择模块输出的默认操作。必须从背板上卸下模块才能设置此开关。请注意,模块上有两个DIP开关。此模块仅使用上部开关。输出默认DIP开关关闭(左)=保持最后状态打开(右)=IC694MDL754不使用强制关闭当输出默认开关处于右(打开)位置时,输出模式设置为强制关闭。在该模式下,只要与CPU的通信中断,输出将变为零。当开关处于左侧位置时,输出默认模式设置为保持最后状态。在该模式下,只要与CPU失去通信,且存在现场电源,输出将保持其最后编程值。
The corresponding output is open
The 32 green/yellow LEDs on the module indicate the on/OFF status of points 1 to 32. These LEDs are green when the corresponding output is turned on and yellow if the output fails. When the corresponding outputs are turned off, they are turned off. Two green/yellow LEDs indicate whether each isolated output group has field power. If the field power is within the limit, it is green. Yellow if there are spot faults in the group. When the on-site power supply does not exist or exceeds the operating limit, they will be turned off. When the module's removable terminal block is locked in place, the module's red/green terminal block LED is green. When the terminal block is unlocked, it is red. If there is an unrecoverable module fault, the junction box LED will flash. The module also sends an add or lose terminal block message to the RX3i CPU to report the terminal block status. Set Output Defaults The DIP switch on the back of the module selects the default operation of the module output. You must remove the module from the backplane to set this switch. Note that there are two DIP switches on the module. This module uses only the upper switch. Output default DIP switch off (left)=Keep the last state open (right)=IC694MDL754 Do not use forced close When the output default switch is in the right (open) position, the output mode is set to forced close. In this mode, as long as the communication with the CPU is interrupted, the output will become zero. When the switch is in the left position, the output default mode is set to hold last. In this mode, as long as communication with the CPU is lost and there is a field power supply, the output will maintain its last programmed value.
模块软件配置
用DIP开关进行的输出默认选择必须与模块软件配置中为此功能进行的选择相匹配。如果两者不匹配,则发生故障。下表总结了带和不带背板电源和现场(外部)电源的输出默认模式的操作。背板功率场功率输出默认操作开启、强制关闭或保持最后状态正常操作。如果检测到模块故障,输出设置为零。On Off Force Off或Hold Last State Module(开-关强制关闭或保持最后状态模块)检测到现场电源丢失,在将输出设置为Off状态时将故障通知CPU。现场电源恢复后,输出保持在关闭状态,直到模块从CPU接收到新的输出数据。点LED指示无现场电源的期望输出。强制关闭模块检测到通信丢失,并在400毫秒内关闭输出。LED熄灭。关闭-保持-最后状态模块检测到通信丢失,并保持输出的最后状态,直到CPU发送新的输出数据。LED熄灭
Module software configuration
The default selection of outputs with DIP switches must match the selection made for this function in the module software configuration. If the two do not match, a fault occurs. The following table summarizes the operation of the output default mode with and without backplane power and field (external) power. The default operation of backplane power field power output is on, forced off, or maintained in the last state. If a module fault is detected, the output is set to zero. The On Off Force Off or Hold Last State Module detects that the field power is lost, and notifies the CPU of the failure when the output is set to the Off state. After the on-site power supply is restored, the output remains in the off state until the module receives new output data from the CPU. The dot LED indicates the desired output without field power. The forced shutdown module detects a loss of communication and shuts down the output within 400 milliseconds. The LED is off. The off hold last status module detects the loss of communication and maintains the last status of the output until the CPU sends new output data. LED off