动叶及变频器禁止同时投入自动。MVe2变频器输入采用单相PWM整流、谐波极小,这样使得输入变压器二次侧绕组不需要移相,结构变得简单;同时采用三电平IGBT串联输出,提高了单元耐压等级、减少了单元数量使得输入变压器二次侧绕组数量大大减少、工艺更简单可靠。MVe2变频单元的硬件构成整流:IGBT、逆变:IGBT为三菱原装产品,中间直流回路电容:可自愈式金属薄膜电容,使用寿命长。
12P3162X162模块,SLS1508使用进展变频装置保护配置:一次风机原10kV电源开关保护配置不变,作为旁路运行方式的保护。在变频器上口开关柜配置CSC241C、保护装置中设置第二套定值作为变频方式运行的变压器主保护。变频装置本体保护和电机的各种保护由变频装置自身保护功能实现。
2.6 紧急停机:变频装置自身带有紧急停机按钮。另外在电动机事故按钮增加一对常开接点,接至变频装置用来在电动机故障时就地同时切除变频装置运行。
4 控制及逻辑说明
(1)变频运行方式
正常运行期间两台一次风机变频自动运行,动叶手动放置在60~80%开度,通过变频器自动调节风机转速,调整一次风压;
(2)工频运行方式
两台风机均工频运行期间,保持原逻辑不变,通过调整风机动叶自动调节一次风压;
(3)一台变频一台工频运行
1)变频器投入自动调节一次风压,工频运行风机手动调节动叶开度,调整两台风机出力平衡;
2)工频运行风机动叶投入自动调节一次风压,变频运行风机手动调节转速,调整两台风机出力平衡;
3)动叶及变频器禁止同时投入自动。某水电站250/50/10t慢速双梁单小车桥式起重机,主要用于电站水轮发电机组及其辅助系统设备的安装、运行维护和检修的吊装任务,也用于电站建设期间设备安装、检修及一般装卸作业。起重机整体按A3工作级别进行设计, 起重机主要由桥架结构、大车运行机构、小车(分别含有起升和小车运行机构)、电动葫芦以及电气设备五大部分及其附件组成。四机构均采用施耐德ATV71变频器进行调速,全车采用PLC进行控制。
management is naturally inaccessible.
2. If the model with management is confirmed, it is necessary to determine whether the management IP address is correct. The factory default management IP of gaonet industrial switch is 10.10.10.1.
If the IP address is manually modified, please log in to the industrial switch with the modified IP. If you forget after manual modification, please restore the factory IP to the default 10.10.10.1, or connect the serial port to enter the command background of the industrial switch to view the management IP information (we have sent the operation manual before for specific operation, which can be operated according to the instructions in the manual). After confirming the management IP of the industrial switch, Ping the management IP of the industrial switch with the ping command. If you can ping, you can enter the web interface under normal circumstances.
If you can't get in, there may be the following reasons: first, the IP address conflicts, and the management IP of the industrial switch is duplicate with that of other devices. In this case, temporarily disconnect the industrial switch from other equipment, clean up ARP and re-enter. The possibility of IP conflict is eliminated. You can ping the management IP, but you can't enter the web management. At this time, please clean the browser cache and ARP. After cleaning the browser cache, close the browser, then open the browser and enter the management IP. 1.