WOODWARD 8446-1019工控调速器,8446-1019中文PDF使用手册
固件版本为3.10或更低的模块
版本可能报告意外和高度间歇性的输入/输出丢失
VersaMax模拟输入模块的模块故障
IC200ALG240、IC200ALG620和IC200ALG630;模拟输出模块,IC200ALG331;混合离散/高速计数器模块,IC200MDD841;和串行通信模块,IC200CMM020。对于大多数用户来说,这些故障永远不会发生。此问题已在IC200GBI001固件中更正版本3.20。
VersaMax模拟输入模块IC200ALG240、IC200ALG620和IC200ALG630安装在具有NIU固件的Genius输入/输出站中

WOODWARD 8446-1019工控调速器版本3.20必须升级到固件版本1.20或更高版本。以前版本的模拟输入模块固件可能会产生与任何版本一起使用时,意外丢失I/O模块故障的Genius NIU固件,包括版本3.20。一个完全模拟模块固件中的不同问题导致这些故障。但是,输入/输出故障表条目中的故障是由这两个问题引起的包含相同的故障位置和额外的数据信息。限制和未决问题
▪ 当新配置的存储被中断时(例如卸下串行电缆),Genius NIU通常会恢复
操作以匹配以前的配置。但是,如中断发生在某个2秒窗口内,Genius
NIU不会恢复增强诊断操作。EDMLED将熄灭。重新尝试存储新配置,或关闭GNIU电源以恢复到以前的配置。
modules with firmware version 3.10 or earlier
versions may report unexpected and highly intermittent Loss of I/O
Module faults for the VersaMax analog input modules
IC200ALG240, IC200ALG620 and IC200ALG630; the analog
output module, IC200ALG331; the Mixed Discrete / High-Speed
Counter Module, IC200MDD841; and the Serial Communications
module, IC200CMM020. These faults never occur for most users.
This issue has been corrected in IC200GBI001 firmware
version 3.20.
VersaMax analog input modules IC200ALG240, IC200ALG620 and
IC200ALG630 installed in a Genius I/O station with NIU firmware
version 3.20 must be upgraded to firmware version 1.20 or later.
Previous versions of analog input module firmware may produce
unexpected Loss of I/O Module faults when used with any version
of Genius NIU firmware, including version 3.20. An entirely
different issue in the analog module firmware causes these faults.
However, I/O Fault table entries for the faults caused by both issues
contain identical Fault Location and Extra Data information.
Restrictions and Open Issues
▪
When a store of a new configuration is interrupted (for example, by
removal of the serial cable), the Genius NIU generally reverts
operation to match the previous configuration. However, if the
interruption occurs during a certain 2-second window, the Genius
NIU does not restore Enhanced Diagnostics operation. The EDM
LED will be OFF. Re-try the store of the new configuration, or
power-cycle the GNIU to revert to the previous configuration.