HESG441635R1主控板卡,HESG441635R1使用在哪里
冗余输入电压24 V DC,在符合NAMUR
电源输出提供:
SD 802F:5 V DC/5 A和3.3 V DC/5 A
SD 812F:5 V DC/5.5 A和3.3 V DC/6.5 A
增强的电源故障预测和停机程序
LED指示电源状态和工作状态
AC 800F的状态
防短路,限流
主电源情况下使用的20 ms备用电能

HESG441635R1主控板卡根据NAMUR的说法,失败描述AC 800F模块配备5 V DC/5 A和SD 802F电源的3.3 V DC/5 A辅助电源模块,分别。5 V DC/5.5 A和3.3 V DC/6.5 ASD 812F。电源具有断路、过载和持续短路保护。电子控制输出电压提供高稳定性和低残余纹波。
在断电的情况下≥ 5 ms时,电源模块发出电源故障信号。该信号由CPU模块使用
关闭操作并进入安全状态。这是在电源恢复时控制重启系统和用户应用程序所必需的。输出电压保持不变在其公差范围内至少再保持15 ms将管理20 ms的输入电压降。
LED显示屏权力绿色内部电源电压可用失败
非正常状态橙色自检
运行期间出现闪烁橙色过热基本单元的红色硬件故障系统软件故障闪烁红色
运行/停止绿色处理活动闪烁绿色进程已停止,现在已启动再一次红色处理未激活闪烁红色进程处于活动状态,现已停止橙色自检
非软件初始化Prim/Sec如果存在冗余,请参阅LED在手册“安装和安装说明”。
对于非冗余,状态为:橙色自检非正常状态
Features
Redundant input voltage 24 V DC, provides operation in
accordance with NAMUR
Power supply outputs provide:
SD 802F: 5 V DC / 5 A and 3.3 V DC / 5 A
SD 812F: 5 V DC / 5.5 A and 3.3 V DC / 6.5 A
Enhanced power-fail prediction and shutdown procedures
LED indication for power supply status and operating
status of the AC 800F
Short circuit proof, current limited
20 ms backup energy for use in the event of primary power
failure, according to NAMUR
Description
The AC 800F modules are supplied with 5 V DC / 5 A and
3.3 V DC / 5 A auxiliary power by the SD 802F power supply
module, resp. with 5 V DC / 5.5 A and 3.3 V DC / 6.5 A by the
SD 812F. The power supply has open-circuit, overload and sus
tained short-circuit protection. The electronically controlled out
put voltage provides high stability and low residual ripple.
In case of power loss ≥ 5 ms, the power supply module gener
ates a power-fail signal. This signal is used by the CPU module
to shut down operations and enter to a safe state. This is re
quired for a controlled restart of the system and the user appli
cation when power is restored. The output voltage remains
within its tolerance limits for at least another 15 ms. Altogether
an input voltage drop of 20 ms will be managed.
LED Displays
Power
Green Internal supply voltage is available
Failure
Off Normal status
Orange Self test
Flashing orange Overtemperature occurred during opera
tion
Red
Hardware failure of the basic unit
Flashing red Software failure of the system
Run/Stop
Green Processing active
Flashing green Process was stopped and is now started
again
Red Processing inactive
Flashing red Process was active and is stopped now
Orange Self test
Off Software initialization
Prim/Sec In case of redundancy please see the
LED’s meaning in manual “Mounting and
Installation Instruction”.
For not redundancy the states are:
Orange Self test