HONEYWELL FC-PSU-UNI2450U V2.1机器人模块, FC-PSU-UNI2450U V2.1说明书文档
某些总线状况可能会影响网络输入/输出
事件,如冗余总线的同时切换、部分总线断开(其中一个
双绞线)或其他总线在潜在仲裁器上断开可能会导致网络。
无法通过TCP/IP存储硬件配置
无法通过FIP TCP/IP成功存储硬件配置
FC-PSU-UNI2450U V2.1
未设置通用输入数据的点故障触点
当无法成功使用通用设备的COMV时,点故障
未设置通用输入数据的联系人。他们总是很清楚。但是,如果
生成通用数据的设备丢失,用户故障触点设置正确。
Ping 3000字节或更多的消息可能会导致FBC挂起
如果向FBC发送3000字节或更多的Ping消息,可能会导致挂起或
HONEYWELL FC-PSU-UNI2450U V2.1机器人模块
使FBC模块崩溃。
Certain Bus Conditions May Affect Network I/O
Events such as simultaneous switching of redundant busses, partial bus breaks (one of
twisted pair), or a different bus broken on potential arbiters may cause glitches of I/O on
the network.
Hardware Configuration Cannot Be Stored via TCP/IP
The hardware configuration cannot be successfully stored through a FIP TCP/IP
connection.
Point Fault Contacts For Generic Input Data Are Not Set
When a COMV from a generic device cannot be consumed successfully, the point fault
contacts for the generic input data are not set. They are always clear. However, if the
device that produces the generic data is lost, the subscriber fault contact is correctly set.
Ping Messages of 3000 Bytes or More May Cause the FBC to Hang
If a Ping message of 3000 bytes or more is sent to the FBC, it may result in hanging or
crashing the FBC module.